GB 10876-89 Test method for medium-sized piston single-stage refrigeration compressors

GB 10876-89 Intermediate Piston Type Single-stage Refrigeration Compressors Test Method 1. Scope This standard applies to the product performance test of single-stage piston type intermediate refrigeration compressors. 2. Normative References The following documents contain provisions which, t......

GB 10876-89 Intermediate Piston Type Single-stage Refrigeration Compressors Test Method

1. Scope

This standard applies to the product performance test of single-stage piston type intermediate refrigeration compressors.

2. Normative References

The following documents contain provisions which, through reference in this text, constitute provisions of this standard. For dated references, subsequent amendments (excluding amending errors in the text) or revisions do not apply to this standard. However, all parties using this standard should study whether the latest edition of these documents applies. For undated references, the latest edition of the documents referred to applies.

GB/T 191-2008. Packaging – Pictorial Marking for Handling of Goods

GB/T 486-2008. Volumetric Calibration of Gauges and Flowmeters

GB/T 658-1986. Safety Standard Grades and Markings for Refrigerating and Heat Pump Appliances

GB/T 2423.1-2008. Environmental Testing – Part 1: General and Guidance

GB/T 2423.2-2008. Environmental Testing – Part 2: Tests. A: Cold

GB/T 2423.5-2008. Environmental Testing – Part 5: Tests. Ea and Guidance: Combined Temperature/Humidity Cyclic Test.

GB/T 3000-2013. Refrigeration and Freezing – Safety Features of Refrigeration and Air-Conditioning Machines

3. Terms and Definitions

3.1

Designation of refrigeration compressors

Refrigeration compressors shall be designated according to the design feature, how to drive and the method of cooling, and can form “type” such as direct connected, belt driven and air-cooled type and water-cooled type (always indicated by the first letter “N”).

3.2

Rated power input

The power input to the compressor under the rated operating condition.

3.3

Rated operating condition

Refers to the operating condition prescribed by the manufacturer (namely the compressor inlet and outlet temperature and pressure, condenser type).

4.Product Test

4.1

Basic environmental conditions

Under the basic environmental conditions defined in GB/T 3000-2013, the product performance test shall be carried out.

4.2

Rate of operation

The product performance test shall be performed at the operating rate defined in the product nameplate.

4.3

Test method

Implement the product performance test according to GB/T 2423.1-2008 and GB/T 2423.2-2008, and combined temperature and humidity cyclic test according to GB/T 2423.5-2008.

4.4

Test device and equipment

4.4.1

The accuracy of the test device and instrument shall meet the requirements of GB/T 486-2008, and the accuracy of the flowmeter shall meet the requirements of GB/T 658-1986.

4.4.2

The equipment for refrigerant filling, liquid injection and flow measurement for the product performance test shall meet the relevant requirements.

4.4.3

The interconnected piping of refrigerant from the compressor inlet, then to the vapor-liquid separator, the filter, the pressure controller and the flowmeter, and finally to the outlet side is designed to have no throttling and no cavitation.

4.5

Performance test

Implement the following test:

4.5.1

Evaporation temperature test

Measure the evaporation temperatures at the inlet and outlet of the compressor with appropriate thermometers and pressure measuring instruments (temperature difference should not be more than 0.5℃).

4.5.2

Compression ratio test

Measure the pressure before and after the compressor and calculate the compression ratio.

4.5.3

Power input test

Measure the power and the current input to the compressor and the power factor.

4.5.4

Flow rate test

Measure the refrigerant flow rate at the inlet and outlet of the compressor.

4.5.5

Total power test

For the compressor equipped with oil pump and fan, the total power shall be tested.

4.5.6

Vibration and noise test

Measure the vibration and noise value at the position where the product is supposed to be used.

5.Test reports

5.1

The product performance test report shall include the following items:

A) Date and place of the test;

B) Name, model and technical parameters of the tested products;

C) Test focus and performance index, test result and test value;

D) Test equipment and measuring instruments.

5.2

The performance test report shall be signed and stamped, and the product nameplate information shall be the basis for test results identification.

6. Marking and Packaging

The marking and packaging requirements for refrigeration compressors are defined in GB/T 191-2008.

7. Field Test

Compressors must be tested under actual field conditions, including power input test, compression ratio test, refrigeration capacity test, vibration and noise test, mechanical vibration test and insulation test.

8. Transportation, Storage and Installation

To ensure the normal use of the compressor, before the refrigeration system is put into operation, it is necessary to familiarize with the relevant requirements of the product nameplate and the product manual, and correctly install and release the refrigerant. After the product is released and stored, it should check whether the product is damaged and aging.

9. Regular Maintenance

Regular maintenance of refrigeration compressors can ensure that it can be used for a long time and can ensure that the performance of the compressor can be kept in good condition. The instructions for regular maintenance must be known in order to ensure that the required pressure and temperature are reached, and safety measures must be taken.

Conclusion

This standard specifies the product performance test requirements for intermediate piston type single-stage refrigeration compressors. It is universaly recognized that a well-designed and completed product test can help to ensure that refrigeration compressors meet their performance and safety regulatory requirements. As a result, manufacturers of intermediate piston type single-stage refrigeration compressors should strictly implement the requirements of this standard to ensure the quality of their products.